UK

VENTCROFT

 

DHTML Menu By Milonic JavaScript

   |  Products  |  Fire  |  Fire Performance Cables  | NoBurn Plus
 

Ventcroft Enhanced Fire Performance Cables

 


    

Red and White Enhanced Fire Cable

 

 
Please click here to
download leaflet

 

Enhanced level Fire Cable is now used for most schools, colleges, public buildings or large complex buildings where the very best protection is required. An ‘Enhanced’ Fire Cable is tested to provide a guaranteed 2 hour duration with the cable under Fire  and Mechanical Shock conditions with Water applied for the final hour at a temperature of 930 degrees C. NoBurn Plus is BASEC & LPCB approved to meet the 'Enhanced' standard of BS 5839-1 2013 Clause 26.2e, BS 8434 - 2:2003 120 minutes and BS EN 50200 Class PH30, PH60 & PH120. Now also BASEC approved to BS 8519 Category 2.

NoBurn Plus's design adds simple but effective strength and makes NoBurn Plus fire cable the fastest enhanced cable to install and prepare for installation. The outer sheath and foil are adhered so together are removed at the same time, no time consuming multiple sheaths, foils, wraps or mica tapes to remove.

More flexible than most enhanced fire cable, NoBurn Plus stays where you put it - simple and easy to dress and position in conduit or trunking. NoBurn Plus cores are manufactured with multiple twists to provide the highest level of data protection , ideal  for long cable runs and analogue addressable fire systems. NoBurn Plus soft skin fire cable provides a cost effective quick to install alternative to MICC cables.

Also suitable for automatic lift doors, air conditioning and computer control where low smoke, fume and zero halogen cable is required.

 

 Features

Fastest Enhanced Fire Cable to Prepare for Termination
Easy to Install and Superb Working Flexibility
Up to 12 Twists per metre for Data Protection
Full Size CPC (Earth Core)
Red and White Outer Sheaths Available
1.0mm²,1.5mm² & 2.5mm² Conductors
100m, 200m, 500m and Special Lengths Available
Copper / Co-polymer Foil Screen
Low Smoke & Zero Halogen
Voltage Rating 300v/500v
Suitable for Zone 1 and Zone 2 Hazardous Area Use
Suitable for Air Conditioning, Computer Control & Lift Doors where Low Smoke & Zero Halogen is required
 Approved and Certified to meet

BS 5839-1:2013 Clause 26.2e

'Enhanced' Fire Cable
BS 8519:2010 Category 2 Fire Resistance Standard
BS 8434-2:2003 120 mins. Fire Resistance Standard
BS EN 50200:2006 PH30, PH60 & PH120 Fire Resistance Standard
BS 7629-1:2008 Fire Resistance Standard
BS 6387:1994 Clause 11 CWZ Fire Resistance Standard
BS EN 50267-2-1:1999 Halogen Emission Standard
BS EN 61034-2:2005 Low Smoke Standard
 Also suitable for
Emergency Lighting Standard BS 5266-1:2011
Voice Alarm Systems Standard BS 5839-8:2013
Voice Communication Standard BS 5839-9:2013

back to top

 Accreditations and third Party Certification

LPCB Quality Management
ISO9001:2008 Certification
LPCB Product Certificate 682d


 

BASEC Quality Management
ISO9001:2008 Certification
BASEC
BS 5839-1:2013 Certificate
BASEC
BS 7629-1:2008 Certificate

BASEC
BS 8519
:2010

Certificate

 

 Manufacturers Recommended Installation Guide Lines


Recommended metal clip spacing 300mm Horizontal, 400mm Vertical

Recommended Cable Tray Fastening - Metal Tie, spacing every 1.5 metres.

Installation Temperatures:
Minimum installation Temperature
0ºc
Maximum installation Temperature 70 C

Operating Temperature Temperature:
Minimum -40 C to Maximum +90 C

The cable should not be flexed or bent when either the cable or operating temperature is below the recommended installation temperatures.

Minimum Bend Radius = 6 x Diameter
Plastic Clips or ties must not be used as the sole means of support for fire cable.

 

back to top

BS 5839-1:2013

The Standard BS 5839 (fire detection and fire alarm systems for buildings - Code of practice for system design, installation, commissioning and maintenance) relates to the use and standards of Fire Performance Cables.

More Information

back to top

Downloads

The download drop down box allows you to download files for the products on this page. Files include, Instruction Manuals, Sales leaflets, Specifications and Certificates. Adobe Acrobat Reader may be required to read some of the file, a link is included to download the reader if you require it.Get Adobe Reader


 

back to top

NoBurn Plus Enhanced Fire Performance Cable

         Red

Red 1.5mm Cores & CPC Earth

Reel Cores Code Pallet Min Qty Trade Per 100m

 

 

 

 

1.5mm

100m 2 Cores & CPC VNP-215ERH 60 1 TBA

1.5mm

100m 3 Cores & CPC VNP-315ERH 60 1 TBA

1.5mm

100m 4 Cores & CPC VNP-415ERH 60 1 TBA

1.5mm

200m 2 Cores & CPC VNP-215ERH200M 20 1 TBA

1.5mm

200m 4 Cores & CPC VNP-415ERH200M 20 1 TBA

1.5mm

500m 2 Cores & CPC VNP-215ERH500M 10 1 TBA

1.5mm

500m 4 Cores & CPC VNP-415ERH500M 10 1 TBA

Red 2.5mm Cores & CPC Earth Reel Cores Code Pallet Min Qty Trade Per 100m

2.5mm

100m 2 Cores & CPC VNP-225ERH 60 1 TBA

2.5mm

200m 2 Cores & CPC VNP-225ERH200M 20 1 TBA

2.5mm

500m 2 Cores & CPC VNP-225ERH500M 10 1 TBA

1.0mm & 4.0mm conductor types in 2, 3, & 4 core and other combination are also available,
including white and black sheaths, MOQ may apply.

*Cable prices will vary due to changes to copper costs*

back to top

Fire Performance Cable Part Code Break Down

VFP-215ER

VNP - 2 15 E R H  
Product Type   Conductors CSA CPC Type Outer Sheath Colour Core Colours Length
Ventcroft Fire Performance
Cable "NoBurn Plus"

 

  2 - 2 Core

4 - 4 Core

10 - 1.0mm

15 - 1.5mm

25 - 2.5mm

E - CPC & Screen
 
R - Red

W - White

H- Harmonised Colours

- Old Colours

 

- 100M

50 - 50M

500 - 500M

750 - 750M

(M = Meter)

 

 Revised:08/01/2015

 
 
         
back to top
 
 

arrow.gif © Copyright 1991-2011 Ventcroft Ltd.